ВБВнг(А)-LS

Image "avbvng-ls-vbvng-ls"

Flame-retardent low smoke armoured power cables. The cables meet the requirements of Specs.16.К71-090-2002.

Аpplication

The cables are designed for power transmission and distribution in stationary equipment for alternating voltage 1kV and frequency up to 100Hz.

The cables may be used in d.c. voltage power systems with rating 2,5 times higher than relevant direct voltage. The cables are used for installation in cable structures, indoor and subway, including areas with danger of fire and explosion, if cable is not exposed to considerable stretching effects (cable АВБВнг-LS, with the exception of fire dangerous areas, class B-1 and B-2). Single conductor cables are intended for use in a.c. voltage power systems. Cables are flame-retardent while bundled installation. Fire danger class of the cable is П1.7.2.2.

Specifications

Type of climatization UHL and B, allocation category 1 and 5 as per national standard GOST 15150-69.

Operating temperature range (relative air humidity at the temperature up to +35°С-up to 98%) -50°С to +50°С
Cable Installation and assembly without preheating not lower than -15°С
Minimal bending radius when laid:
  • single conductor cables — 15 outer diameters
  • multi conductor cables — 7,5 outer diameters
Guaranty service life 5 years, but not later than 6 months from the date of manufacturing.
Service life not less than 30 years